Интернет-магазин Электроконтроль Харьков (ex ЧП)
contact@electrocontrol.com.ua
el_c@ukr.net
skype: electro_ukr
Viber, WhatsApp, Telegram: +380667918319
+38 (097) 648-30-48
с 9 до 17 ПН-ПТ

Soft starter, 3p, 32A, 200-480VAC, us=24VAC/DC EATON DS7-340SX032N0-N 134914

Наличие: В наличии
Срок поставки: 2 дней
Гарантия: 12 месяцев
Рейтинг:
Производитель: Eaton (Moeller)

12 365 грн с НДС  X  
Опт: 11129 грн (при сумме покупки от 40 000 грн, применяется менеджером в ручном режиме)
Description     With internal bypass contacts
Function     Soft starters for three-phase loads
Mains supply voltage (50/60 Hz) ULN V AC 200 - 480
Supply voltage Us   24 V AC/DC
Control voltage UC   24 V AC24 V DC
Assigned motor rating (Standard connection, In-Line)      
at 400 V, 50 Hz P kW 15
at 460 V, 60 Hz P HP 25
Rated operational current      
AC-53 Ie A 32
Rated operational voltage Ue   200 V230 V400 V480 V
Connection to SmartWire-DT     no
Frame size     FS2
General
Standards     IEC/EN 60947-4-2UL 508CSA22.2-14
Approvals     CE
Approvals     ULCSAC-TickUkrSEPRO
Climatic proofing     Damp heat, constant, to IEC 60068-2-3Damp heat, cyclic, to IEC 60068-2-10
Ambient temperature      
Operation ϑ °C -5 - +40up to 60 at 2% derating per Kelvin temperature rise
Storage ϑ °C -25 - +60
Altitude   m 0 - 1000 m, above that 1 % derating per 100 m , up to 2000 m
Mounting position     Vertical
Degree of protection      
Degree of Protection     IP20
Protection against direct contact     Finger- and back-of-hand proof
Overvoltage category/pollution degree     II/2
Shock resistance     8 g/11 ms
Vibration resistance to EN 60721-3-2     2M2
Radio interference level (IEC/EN 55011)     B
Static heat dissipation, non-current-dependent Pvs W 1.5
Weight   kg 0.4
Main conducting paths
Rated operating voltage Ue V AC 200 - 480
Supply frequency fLN Hz 50/60
Rated operational current Ie A  
AC-53 Ie A 32
Assigned motor rating (Standard connection, In-Line)      
at 230 V, 50 Hz P kW 7.5
at 400 V, 50 Hz P kW 15
at 200 V, 60 Hz P HP 10
at 230 V, 60 Hz P HP 10
at 460 V, 60 Hz P HP 25
Overload cycle to IEC/EN 60947-4-2      
AC-53a     32 A: AC-53a: 3 - 5: 75 - 10
Internal bypass contacts    
Short-circuit rating      
Type “1” coordination     PKM0-32 (+ CL-PKZ0)
Type „2“ coordination (additional with the fuses for coordination type „1“)     3 x 170M1366
       
Fuse base (number x part no.)     3 x 170H1007
Terminal capacities
Cable lengths      
Solid   mm2 1 x (0.75 - 16)2 x (0.75 - 10)
Flexible with ferrule   mm2 1 x (0.75 - 16)2 x (0.75 - 10)
Stranded   mm2 1 x 16
Solid or stranded   AWG 18 - 6
Tightening torque   Nm 3.2
Screwdriver (PZ: Pozidriv)   mm PZ2; 1 x 6 mm
Control cables      
Solid   mm2 1 x (0.5 - 2.5)2 x (0.5 - 1.0)
Flexible with ferrule   mm2 1 x (0.5 - 1.5)2 x (0.5 - 0.75)
Stranded   mm2 1 x (0.5 - 1.5)2 x (0.5 - 1.0)
Solid or stranded   AWG 1 x (21 - 14)2 x (21 - 18)
Tightening torque   Nm 1.2
Screwdriver   mm 0,6 x 3,5
Control circuit
Digital inputs      
Control voltage      
DC-operated   V DC 24 V DC +10 %/- 15 %
AC operated   V AC 24 V AC +10 %/- 15 %
Current consumption 24 V   mA  
External 24 V   mA 1.6
Pick-up voltage   x Us  
DC-operated   V DC 17.3 - 27
AC operated   V AC 17.3 - 27
Drop-out voltage x Us    
DC operated   V DC 0 - 3
AC operated   V AC 0 - 3
Pick-up time      
DC operated   ms 250
AC operated   ms 250
Drop-out time      
DC operated   ms 350
Regulator supply      
Voltage Us V 24 V AC/DC +10 %/- 15 %
Current consumption Ie mA 50
Notes     External supply voltage
Relay outputs      
Number     2 (TOR, Ready)
Voltage range   V AC 250
AC-11 current range   A 1 A, AC-11
Soft start function
Ramp times      
Acceleration   s 1 - 30
Deceleration   s 0 - 30
Start voltage (= turn-off voltage)   % 30   100
Start pedestal   % 30 - 100
Fields of application      
Fields of application     Soft starting of three-phase asynchronous motors
1-phase motors    
3-phase motors    
Functions
Fast switching (semiconductor contactor)     - (minimum ramp time 1s)
Soft start function    
Reversing starter     External solution required
Suppression of closing transients    
Suppression of DC components for motors    
Potential isolation between power and control sections    
Notes
Rated impulse withstand voltage: 1.2 µs/50 µs (rise time/fall time of the pulse to IEC/EN 60947‐2 or ‐3) Applies for control circuit/power section/enclosure

Soft starter, 3p, 32A, 200-480VAC, us=24VAC/DC EATON DS7-340SX032N0-N 134914 габаритные размеры

габаритные размеры soft starter, 3p, 32a, 200-480vac, us=24vac/dc eaton ds7-340sx032n0-n 134914 

Отзывы / Вопросы

Добавить вопрос/отзыв



Аналогичные товары других производителей:




2009 - 2024 Интернет-магазин электрооборудования "Электроконтроль" (ООО НПП "Нафтаенергопром", ex ЧП Электроконтроль) Карта сайта