General |
Standards |
|
|
IEC/EN 60947-4-2UL 508CSA22.2-14 |
Approvals |
|
|
CE |
Approvals |
|
|
ULCSAC-TickUkrSEPRO |
Climatic proofing |
|
|
Damp heat, constant, to IEC 60068-2-3Damp heat, cyclic, to IEC 60068-2-10 |
Ambient temperature |
|
|
|
Operation |
ϑ |
°C |
-5 - +40up to 60 at 2% derating per Kelvin temperature rise |
Storage |
ϑ |
°C |
-25 - +60 |
Altitude |
|
m |
0 - 1000 m, above that 1 % derating per 100 m , up to 2000 m |
Mounting position |
|
|
Vertical |
Degree of protection |
|
|
|
Degree of Protection |
|
|
IP20 |
Protection against direct contact |
|
|
Finger- and back-of-hand proof |
Overvoltage category/pollution degree |
|
|
II/2 |
Shock resistance |
|
|
8 g/11 ms |
Vibration resistance to EN 60721-3-2 |
|
|
2M2 |
Radio interference level (IEC/EN 55011) |
|
|
A |
Static heat dissipation, non-current-dependent |
Pvs |
W |
0.2 |
Weight |
|
kg |
0.4 |
Main conducting paths |
Rated operating voltage |
Ue |
V AC |
200 - 480 |
Supply frequency |
fLN |
Hz |
50/60 |
Rated operational current |
Ie |
A |
|
AC-53 |
Ie |
A |
4 |
Assigned motor rating (Standard connection, In-Line) |
|
|
|
at 230 V, 50 Hz |
P |
kW |
0.75 |
at 400 V, 50 Hz |
P |
kW |
1.5 |
at 200 V, 60 Hz |
P |
HP |
0.75 |
at 230 V, 60 Hz |
P |
HP |
1 |
at 460 V, 60 Hz |
P |
HP |
2 |
Overload cycle to IEC/EN 60947-4-2 |
|
|
|
AC-53a |
|
|
4 A: AC-53a: 3 - 5: 75 - 10 |
Internal bypass contacts |
|
|
|
Short-circuit rating |
|
|
|
Type “1” coordination |
|
|
PKM0-4 (+ CL-PKZ0) |
Type „2“ coordination (additional with the fuses for coordination type „1“) |
|
|
3 x 170M1359 |
|
|
|
|
Fuse base (number x part no.) |
|
|
3 x 170H1007 |
Terminal capacities |
Cable lengths |
|
|
|
Solid |
|
mm2 |
1 x (0.75 - 4)2 x (0.75 - 2.5) |
Flexible with ferrule |
|
mm2 |
1 x (0.75 - 2.5)2 x (0.75 - 2.5) |
Solid or stranded |
|
AWG |
18 - 10 |
Tightening torque |
|
Nm |
1.2 |
Screwdriver (PZ: Pozidriv) |
|
mm |
PZ2; 1 x 6 mm |
Control cables |
|
|
|
Solid |
|
mm2 |
1 x (0.75 - 4)2 x (0.75 - 2.5) |
Flexible with ferrule |
|
mm2 |
1 x (0.75 - 2.5)2 x (0.75 - 2.5) |
Solid or stranded |
|
AWG |
18 - 10 |
Tightening torque |
|
Nm |
1.2 |
Screwdriver |
|
mm |
0,8 x 5,51 x 6 |
Control circuit |
Digital inputs |
|
|
|
Control voltage |
|
|
|
AC operated |
|
V AC |
110 V AC - 15 % - 230 V AC +10 % |
Current consumption 24 V |
|
mA |
|
External 24 V |
|
mA |
1.6 |
Current consumption 230 V |
|
mA |
4 |
Pick-up voltage |
|
x Us |
|
AC operated |
|
V AC |
108 - 253 |
Drop-out voltage |
x Us |
|
|
AC operated |
|
V AC |
0 - 15 |
Pick-up time |
|
|
|
AC operated |
|
ms |
250 |
Drop-out time |
|
|
|
AC operated |
|
ms |
350 |
Regulator supply |
|
|
|
Voltage |
Us |
V |
110 V AC -15 % - 230 V AC +10 % |
Current consumption |
Ie |
mA |
50 |
Notes |
|
|
External supply voltage |
Relay outputs |
|
|
|
Number |
|
|
1 (TOR) |
Voltage range |
|
V AC |
= Us |
AC-11 current range |
|
A |
1 A, AC-11 |
Soft start function |
Ramp times |
|
|
|
Acceleration |
|
s |
1 - 30 |
Deceleration |
|
s |
0 - 30 |
Start voltage (= turn-off voltage) |
|
% |
30 100 |
Start pedestal |
|
% |
30 - 100 |
Fields of application |
|
|
|
Fields of application |
|
|
Soft starting of three-phase asynchronous motors |
1-phase motors |
|
|
● |
3-phase motors |
|
|
|
Functions |
Fast switching (semiconductor contactor) |
|
|
- (minimum ramp time 1s) |
Soft start function |
|
|
|
Reversing starter |
|
|
External solution required |
Suppression of closing transients |
|
|
|
Suppression of DC components for motors |
|
|
|
Potential isolation between power and control sections |
|
|
|
Notes |
Rated impulse withstand voltage: 1.2 µs/50 µs (rise time/fall time of the pulse to IEC/EN 60947‐2 or ‐3) Applies for control circuit/power section/enclosure |
Отзывы / Вопросы